407 lines
20 KiB
HTML
407 lines
20 KiB
HTML
<!DOCTYPE html>
|
|
<html lang="en">
|
|
<head>
|
|
<meta charset="UTF-8">
|
|
<meta name="viewport" content="width=device-width, initial-scale=1">
|
|
<title>Residential Wood Stove Installation — GigaChad</title>
|
|
<link rel="icon" href="/favicon.ico">
|
|
<link rel="stylesheet" href="/style.css?v=1">
|
|
<meta property="og:type" content="website">
|
|
<meta property="og:title" content="Residential Wood Stove Installation — GigaChad">
|
|
<meta property="og:description" content="The greatest website on the interwebz!">
|
|
<meta property="og:image" content="/icons/chads/chad.png">
|
|
</head>
|
|
<body>
|
|
<script>
|
|
const setTheme = () => {
|
|
const root = document.documentElement
|
|
const storage = localStorage.length > 0 ? localStorage : sessionStorage
|
|
for (let key in storage) {
|
|
if (storage.hasOwnProperty(key)) {
|
|
root.style.setProperty(key, storage.getItem(key))
|
|
}
|
|
}
|
|
}
|
|
setTheme()
|
|
document.addEventListener('visibilitychange', () => { if (!document.hidden) setTheme() })
|
|
</script>
|
|
<h1>Residential Wood Stove Installation</h1>
|
|
<div style="text-align: center;">
|
|
<a href="/"><img class="epic" src="/icons/chads/chad.png"></a>
|
|
</div>
|
|
<hr>
|
|
<p class="nav"><span class="nav-left">Listed under <a href="/practical-skills.html">Practical Skills</a>.</span><span class="nav-right"><a href="/theme.html">Theme</a></span></p>
|
|
<p>From the <a href="https://www.extension.purdue.edu/extmedia/fnr/FNR-100.html" target="_blank">original article</a>.</p>
|
|
<p>
|
|
Wood, when readily available, is a cheap source of home
|
|
fuel. Unfortunately, house fires can occur when stoves are improperly
|
|
installed or carelessly operated and maintained.
|
|
</p><p>
|
|
This publication, using National Fire Prevention Association (NFPA)
|
|
standards, describes proper installation of radiant-type
|
|
wood-burning room heaters in residential homes. These standards are
|
|
the basis of many building codes. Recommendations will vary for
|
|
furnaces, circulating stoves, cook stoves, and ranges. In all cases,
|
|
you should consult local officials for details and use good sense
|
|
during stove installation, operation, and maintenance. Some states
|
|
recommend that you consult the fire marshall and your insurance agent
|
|
as well as the local building permit office before installing a
|
|
stove.
|
|
</p><p>
|
|
Most fires are caused when combustibles are too close to a hot
|
|
stove, by the escape of hot gases or flames through a crack in a
|
|
chimney, by conduction of heat from the stovepipe or stove to
|
|
combustible material, or by sparks or coals escaping from a stove.
|
|
Protection must be provided for combustible wall, ceiling, and floor
|
|
materials near the stove and stovepipe as well as where the
|
|
stovepipe passes through or near combustible walls, ceilings, and
|
|
other materials.
|
|
</p>
|
|
<h2>Wall Protection
|
|
</h2>
|
|
<p> Stoves and stovepipes must be spaced out from walls and other
|
|
combustible materials to prevent ignition. They should not be
|
|
installed in alcoves, closets, or similar areas. Table 1 shows the
|
|
minimum clearances from combustible walls and ceilings. Wood frame
|
|
walls covered with dry wall are considered combustible.
|
|
</p><p>
|
|
If no wall protection is used, the common radiant-type stove or
|
|
heater must be spaced out at least 36 inches from the wall. This
|
|
distance may be reduced considerably if asbestos millboard and/or 28
|
|
gage sheet metal is used for wall protection. A 1-inch or wider air
|
|
gap between the wall and the asbestos millboard or metal panel must
|
|
be provided. The one-inch spacers must be of a non-combustible
|
|
material. In addition, a 1 1/3 inch or wider air gap is needed at
|
|
the bottom of the asbestos millboard or metal panel. Circulating air
|
|
will cool the panel and wall behind it (Figure 1). At least 36
|
|
inches of clearance must be allowed between the top of a stove and
|
|
an unprotected ceiling. Brick or stone provide little or no protection
|
|
for a combustible wall since they are good conductors of
|
|
heat. Therefore, by themselves, these are not suitable as wall
|
|
protectors. When used, however, they, too, should be spaced out from
|
|
the wall with a gap at the bottom to provide air circulation.
|
|
</p><p>
|
|
There is a simple test that will tell if you have provided enough
|
|
clearance. Place your hand on the closest surface. If you can keep
|
|
your hand there comfortably while the stove is operating, the
|
|
location passes the test. If not, you need added protection.
|
|
</p>
|
|
<h2>Table 1. Minimum clearances from combustible walls and ceilings.*
|
|
</h2>
|
|
<pre>
|
|
Stove type
|
|
Type of protection Radiant Circulating Stovepipe
|
|
--------------------------------------------------
|
|
None 36" 12" 18"
|
|
1/4" asbestos millboard,
|
|
spaced out 1" 18" 6" 12"
|
|
28 gage sheet metal,
|
|
spaced out 1" 12" 4" 9"
|
|
28 gage sheet metal on
|
|
1/8". asbestos millboard,
|
|
spaced out 1" 12" 4" 9"
|
|
--------------------------------------------------
|
|
*From National Fire Protection Association No. 89M, 1976.
|
|
</pre>
|
|
<a href="/files/wood-stove-1.gif" target="_blank"><img class="center" src="/files/wood-stove-1.gif"></a>
|
|
<p class="c">
|
|
Figure 1. Air circulation behind any type of wall
|
|
protection is essential for cooling.
|
|
</p>
|
|
<h2>Floor Protection
|
|
</h2>
|
|
<p> All floors on which stoves are set, except concrete, must be
|
|
protected from the heat of both the fire and hot coals falling out
|
|
when the fuel is added (Figure 2). The NFPA recommends covering the
|
|
floor beneath the stove with No. 24 gage or thicker sheet metal. Metal
|
|
with asbestos backing and asbestos millboard can also be used. If
|
|
slate, brick, etc. are used, they must be mortared in place with no
|
|
gaps. Metal or asbestos millboard must be installed between the
|
|
brick (slate or stone) and the floor.
|
|
</p><p>
|
|
If the stove legs provide less than 6 inches of clearance, 2 to 4
|
|
inches of hollow masonry laid to pro- vide air circulation with a
|
|
sheet of 24 gage sheet metal between the floor and the masonry is
|
|
recommended. Eight- to ten-inch legs will provide more air space, and
|
|
less heat will be transferred to the floor. A 2-inch layer of sand or
|
|
ashes laid in the bottom of the stove will also help prevent
|
|
overheating of the floor.
|
|
</p><p>
|
|
The materials used to protect the floor should extend 12 inches
|
|
beyond the sides of the stove without openings and 18 inches beyond
|
|
the side with the door or other potential openings.
|
|
</p>
|
|
<a href="/files/wood-stove-2.gif" target="_blank"><img class="center" src="/files/wood-stove-2.gif"></a>
|
|
<p class="c">
|
|
Figure 2. Clearances far stove and stovepipe from walls and floor.
|
|
</p>
|
|
<h2>Other Combustibles
|
|
</h2>
|
|
<p> Other combustible materials such as firewood, paper, curtains, and
|
|
plastics should be kept at least 36 inches from the stove.
|
|
</p>
|
|
<h2>Stovepipes
|
|
</h2>
|
|
<p> Like fireplaces, wood-burning stoves must be vented to the outside
|
|
of the building. A stovepipe is used to connect the stove to a masonry
|
|
chimney or prefabricated metal chimney. The stovepipe is sometimes
|
|
referred to as a connector. Single wall 24-gage or thicker
|
|
corrosion-resistant steel stovepipe is recommended. If the stovepipe
|
|
diameter is over 10 inches, a heavier gage metal must be used. The
|
|
diameter of the stovepipe shall be the same diameter as the firebox
|
|
outlet. In some situations, a prefabricated or insulated metal
|
|
chimney may be connected directly to the stove. Table 2 shows common
|
|
chimney capacities required for different sized stoves.
|
|
</p>
|
|
<h2>Table 2. Chimney capacity required by stove size. *
|
|
Area in square inches of flue
|
|
</h2>
|
|
<pre>
|
|
19 28 38 50 78 113
|
|
Total flue Combined input rating of stoves in
|
|
height in feet thousands of BTU/hr
|
|
------------------------------------------------
|
|
6 45 71 102 142 245 NR
|
|
8 52 81 118 162 277 405
|
|
10 56 89 129 175 300 450
|
|
15 66 105 150 210 360 540
|
|
20 74 120 170 240 415 640
|
|
NR means not recommended
|
|
--------------------------------------------------
|
|
*From National Fire Prevention Association No. HS-8, 1974.
|
|
</pre>
|
|
<p>
|
|
Clearances from walls. Stovepipes, like stoves, radiate heat. If
|
|
they are installed close to combustible materials, a fire can
|
|
result. The NFPA recommends that a stovepipe be at least 18 inches
|
|
from the nearest combustible material. Closer clearances are allowed
|
|
in some situations (Table 1).
|
|
</p><p>
|
|
Clearances through walls and ceilings. The NFPA does not permit a
|
|
stovepipe to pass through any floor or ceiling or through any fire
|
|
wall or fire partition. However, if a stovepipe must pass through a
|
|
partition other than a fire partition, one of the following
|
|
conditions must be followed:
|
|
</p><p>
|
|
Combustible materials within 18 inches of an uninsulated
|
|
stovepipe must be removed. For a 6-inch diameter pipe, this requires a
|
|
6-inch plus 2 x 18 inch or a 42-inch diameter hole in a combustible
|
|
wall. This hole may be closed or covered with non-combustible
|
|
insulating materials (Figure 3).
|
|
</p><p>
|
|
The 18 inch clearance may be reduced by using a metal thimble or a
|
|
burned fire-clay thimble and surrounding it with at least 8 inches
|
|
of fireproofing material (Figure 3).
|
|
</p>
|
|
<a href="/files/wood-stove-3.gif" target="_blank"><img class="center" src="/files/wood-stove-3.gif"></a>
|
|
<p class="c">
|
|
Figure 3. One method of passing an uninsulated stovepipe through a
|
|
combustible wall. The 18 inch clearance can be reduced to 8 inches by
|
|
extending the thimble (see dotted line) and surrounding it with at
|
|
least 8 inches of fireproofing material.
|
|
</p><p>
|
|
Where a ventilated type metal thimble is used, the
|
|
thimble must be at least 12 inches larger in diameter
|
|
than the stovepipe (Figure 4).
|
|
</p><p>
|
|
Clearance into chimney. If the stovepipe is connected to a masonry
|
|
chimney, it should extend through the near wall of a chimney to the
|
|
inner face of the chimney liner, but not beyond it. A thimble should
|
|
be cemented with high-temperature cement into the masonry wall of the
|
|
chimney and the stovepipe inserted into the thimble without cement
|
|
for easy removal for cleaning and replacement. If a thimble is used,
|
|
the stovepipe must be in tight enough so that a sudden puff in the
|
|
firebox of the stove will not dislodge the pipe.
|
|
</p><p>
|
|
Lengths. The stovepipe should be as straight and short as
|
|
possible. Long, uninsulated stovepipes may increase heating
|
|
efficiency, but they are discouraged because exhaust gases are
|
|
cooled and creosote can develop more rapidly. Creosote accumulations
|
|
create a serious fire hazard. Additional information on creosote
|
|
deposits follows under "Chimney Fires."
|
|
</p><p>
|
|
Sometimes stovepipes may be used in a horizontal position to
|
|
connect a stove to a chimney. In this case, the NFPA code specifies
|
|
that the horizontal run be limited. If an uninsulated stovepipe is
|
|
used, it shall not be longer than 75 percent of the height of the
|
|
chimney above its point of entry into the chimney. If an insulated
|
|
stovepipe is used, - the horizontal run shall not be longer than 100
|
|
percent of the height of the chimney above its point of entry into the
|
|
chim- ney. The chimney is assumed to be a natural draft. The
|
|
horizontal portion of any stovepipe must have an elevated pitch or
|
|
rise of at least y4 inch per linear foot. The point of connection to
|
|
the chimney must be at the higher elevation than the end nearest the
|
|
stove. Each stovepipe joint should be secured with at least three
|
|
sheet metal screws or the equivalent. The joints should fit tightly
|
|
and overlap by about 2 inches with the crimped (male) end pointing
|
|
down into the next piece. This arrangement will prevent creosote
|
|
leaks. When connecting a stove to a chimney, it is preferred to have
|
|
only one 90 degree elbow. Two can be used, however, when necessary.
|
|
</p><p>
|
|
A damper to help control draft is often installed in the stovepipe
|
|
near the stove. Check the stove manufacturer's or dealer's
|
|
recommendation for details. Automatic draft regulators activated by
|
|
a thermostat may be installed according to manufacturer's directions
|
|
and local codes.
|
|
</p>
|
|
<h2>Chimneys
|
|
</h2>
|
|
<p> Chimneys may be masonry or the prefabricated metal type. Masonry
|
|
chimneys are generally installed when the house is being built. In
|
|
some cases, how- ever, they may be added later. Prefabricated metal
|
|
chimneys can be added anytime and are generally used when a masonry
|
|
chimney is not available.
|
|
</p>
|
|
<a href="/files/wood-stove-4.gif" target="_blank"><img class="center" src="/files/wood-stove-4.gif"></a>
|
|
<p class="c">
|
|
Figure 4. A ventilated metal thimble may be
|
|
used to pass a stovepipe through a combustible partition wall.
|
|
</p><p>
|
|
Masonry chimneys. If an existing masonry chimney is to be used,
|
|
check it for leaks. It should also have a flue lining. If the chimney
|
|
is old and deteriorated or does not have a flue lining,
|
|
prefabricated metal chimneys may be inserted into the old flue.
|
|
</p><p>
|
|
When an existing chimney is used, the cross- sectional area of
|
|
the chimney flue should be at least 25 percent greater than that of
|
|
the stovepipe. This will provide adequate draft for exhausting gases
|
|
from the stove. A stovepipe cannot be connected to a fireplace flue
|
|
unless the fireplace opening is sealed off. It is also acceptable if
|
|
the flue is tightly sealed between the fireplace opening and the
|
|
stovepipe entrance to the flue. Fireplace openings and flues should be
|
|
sealed in such a way that future chimney cleaning is. not hampered.
|
|
</p><p>
|
|
Masonry chimneys should also be constructed with proper flashing
|
|
and saddles to prevent roof leaks.
|
|
</p><p>
|
|
Prefabricated Chimneys. Where masonry chimneys are not available,
|
|
prefabricated chimneys may be used. These chimneys come in short
|
|
sections of various lengths that lock together. They may be of double
|
|
wall construction with insulation packed between each wall or of
|
|
triple wall construction designed in such a way that air circulates
|
|
down one wall cavity and up the other. The inner lining of these
|
|
chimneys is usually of corrosion-resistant stainless steel. To be used
|
|
for wood stoves, these chimneys must be listed as UL ALL FUEL
|
|
chimneys. The necessary clearances from combustible materials are
|
|
marked on each section of a UL-listed prefabricated chimney. For the
|
|
insulated double wall-type chimney, the minimum clearance is usually
|
|
two inches. Prefabricated chimneys are efficient and easy to
|
|
install. Creosote build-up is minimized in the insulated type chimney
|
|
because of rapid warming of the inner walls. However, the triple
|
|
wall-type which circulates the air may cause rapid cooling of the
|
|
flue gases and thus increase creosote formation.
|
|
</p>
|
|
<a href="/files/wood-stove-5.gif" target="_blank"><img class="center" src="/files/wood-stove-5.gif"></a>
|
|
<p class="c">
|
|
Figure 5a. A 3-foot minimum chimney height is required where the
|
|
chimney penetrates the roof line less than 10 feet (measured
|
|
horizontally) from the peak.
|
|
</p><p>
|
|
To keep rainwater from entering the house, prefabricated chimneys
|
|
are usually sold with storm collars and flashings as well as caps
|
|
and spark-arresting screens.
|
|
</p><p>
|
|
Chimney height. For a pitched roof, chimney height must be a
|
|
minimum of 3 feet from where it penetrates the roof or at least 2
|
|
feet above the highest roof surface within 10 feet horizontally
|
|
(Figure 5). On flat roofs, the chimneys must be at least 3 feet above
|
|
the roof. These precautions should prevent down drafts as well as roof
|
|
fires from sparks.
|
|
</p><p>
|
|
Multi-flues. The NFPA recommends that room heaters, cook stoves,
|
|
etc. should not be connected to a common flue. Flue gases and sparks
|
|
may pass from one flue opening to another and explode, or the
|
|
poisonous fumes could seep into the house. Multiple connections may
|
|
also result in unsatisfactory draft, and if a chimney fire does occur,
|
|
it cannot be suffocated.
|
|
</p>
|
|
<a href="/files/wood-stove-6.gif" target="_blank"><img class="center" src="/files/wood-stove-6.gif"></a>
|
|
<p class="c">
|
|
Figure 5b. If there are mare than 10 feet between the
|
|
peak and where the chimney penetrates the roof line,
|
|
then at least 2 additional feet of chimney must be added
|
|
above the 10-foot horizontal measurement.
|
|
</p>
|
|
<h2>Chimney Fires
|
|
</h2>
|
|
<p> Chimney fires result when creosote deposits in the stovepipe are
|
|
ignited - usually by a particularly hot fire. Creosote is formed when
|
|
unburned gases (smoke) are cooled and condense inside the stovepipe
|
|
or chimney. When first formed, creosote is a black liquid, and it may
|
|
seep through cracks in masonry chimneys or joint connections in
|
|
stovepipes. It may later dry and form a crust in the stovepipe or
|
|
chimney. With time, these deposits build up and then finally burn,
|
|
resulting in an intense, hot fire which can ignite nearby combustibles
|
|
and the house roof.
|
|
</p><p>
|
|
Creosote deposits cannot be eliminated. It does help, however, to
|
|
use well-seasoned hardwood as fuel and to run a small hot fire rather
|
|
than a large smouldering one. When starting or adding wood to a fire,
|
|
run the fire hot for 10-20 minutes. This will rapidly heat the wood
|
|
and drive off some of the moisture.
|
|
</p><p>
|
|
Frequent chimney inspections are essential. Check for creosote
|
|
deposits after every cord of wood is burned or at least once a
|
|
year. Creosote deposits build up faster in some situations than
|
|
others. For example, the newer "air tight" stoves are very efficient
|
|
and tend to form creosote deposits faster. Sooner or later, a
|
|
thorough chimney cleaning will be necessary.
|
|
</p>
|
|
<a href="/files/wood-stove-7.gif" target="_blank"><img class="center" src="/files/wood-stove-7.gif"></a>
|
|
<p class="c">
|
|
Figure 6. Creosote and soot deposits loosened from chimney with wire
|
|
brush. These deposits accumulated in less than two months.
|
|
</p>
|
|
<p>
|
|
To clean prefabricated chimneys, many stove dealers sell round wire
|
|
brushes which can be attached to small diameter metal pipes or
|
|
ropes. The pipe or rope with the brush attached is then moved up and
|
|
down in the chimney until all creosote deposits are removed. The
|
|
deposits should fall to the bottom of the chimney and must be
|
|
removed (Figure 6). Although not as effective, burlap bags filled
|
|
with straw and weights such as rocks can be pulled up and down the
|
|
chimney to remove creosote deposits.
|
|
</p><p>
|
|
If a chimney fire does occur, limit the air supply to the
|
|
fire. Discharge a fire extinguisher into the stove and call the fire
|
|
department. A multi-purpose dry chemical (Class ABC) fire extinguisher
|
|
is preferred. This type is appropriate for other home fires as well.
|
|
</p>
|
|
<h2>Summary
|
|
</h2>
|
|
<p> Wood stoves can be an economical source of home heat. However, if
|
|
they are not properly installed, maintained and operated, serious
|
|
house fires and even death can result. This bulletin outlines
|
|
installation procedures as recommended by the National Fire
|
|
Prevention Association. These recommendations are written to apply to
|
|
all situations and, therefore, are general in nature. When installing
|
|
your stove, consult with local officials for details and follow the
|
|
manufacturer's recommendations. Always operate your stove in a
|
|
sensible fashion, and periodically inspect it for damage. Routinely
|
|
clean creosote deposits from the chimney. Keep a fire extinguisher
|
|
present at all times, and guard against complacency.
|
|
</p>
|
|
<h2>Suggested Readings
|
|
</h2>
|
|
<p>
|
|
Chimneys, Fireplaces, and Vents. 1977. National Fire Prevention
|
|
Association, 470 Atlantic Ave., Boston, MA 02210, 50 pp. ($3.00)
|
|
</p><p>
|
|
Heat-Producing Appliance Clearances, 1976. National Fire Prevention
|
|
Association, 470 Atlantic Ave., Boston, MA 02210, 14 pp. ($3.00)
|
|
</p><p>
|
|
Using Wood and Coal Stoves Safely, 1974. National Fire Prevention
|
|
Association, 470 Atlantic Ave., Boston, MA 02210, 12 pp. ($2.00)
|
|
</p><p>
|
|
The Woodburner's Encyclopedia, 1977. Vermont Crossroads Press, Box
|
|
333, Waitsfield, VT 05673, 162 pp. ($7.95)
|
|
</p><p>
|
|
Fireplaces and Chimneys. U.S. Department of Agriculture,
|
|
Agricultural Research Service, Farmers' Bulletin No. 1889, Reprinted
|
|
September 1977.
|
|